Groung Fault Circuit Interrupter
GFD Tabs
Drawing Information |
20 Amp GFCI |
NSN Number |
5999-01-618-2484 |
Part Number |
25980 replaces 33240 |
Key Features
- 20 Amp 240VAC 50/60Hz
- Operating voltage range 204 to 264 VAC
- 4 to 6 mA trip
- Manual Reset
- Panel Mount or Bulkhead Mount
- Flying leads
Standards Compliance
- Operating temperature range -35 degrees C to +66 degrees C
- Tested and Meets 10G High Shock Impact
- Tested and meets 10-55 Hz Vibration